Products

VM-3240VA

System Management Amplifier

  • 1 unit per system
  • 8 remote microphones max. (4x general + 4x emergency;
  • EN 54: max. 2 x emergency or 4 x general +1 x emergency)
  • 240 W power output
  • 6 recorded general announcements and 2 recorded emergency announcements
  • 8 remote microphones max. (up to 4 emergency remote microphones)
  • 6 zones selectable from the front panel
  • Built-in high quality electronic voice message




  • Specifications
  • Equipment
  • Tender text
  • Downloads
Specifications
Specifications for product:
VM-3240VA
Power source

230 V AC, 50 / 60 Hz

Rated output

240 W (total into 6 zones)

Frequency response

50 Hz - 20 kHz (at 1/3 rated output)

Distortion

< 0.7 % (at 1 kHz, rated power)

Power consumption

600 W (at rated output), 260 W (EN 60065)

S/N ratio

85 dB (or more)

Inputs

Input 1 - 3: -50 dBV (MIC) / -10 dB (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female) / phone jack

Input 4: -50 dBV (MIC) / -10 dBV (LINE) (changeable), 600 Ω, electronically balanced, on removable terminal block (14 x 2 pins)

BGM 1 - 2: -10 dBV, 10 kΩ unbalanced, RCA pin jack (2 x 2)

External amplifier Input: 100 V Line, removable terminal block (14 pins)

Outputs

Speaker output 1 – 6: Total within rated output, removable terminal block (14 pins)

Direct output from internal or external amplifier, removable terminal block (16 pins)

Recording output BGM / Paging 0 dBV, 10 kΩ, unbalanced, RCA pin jack

Control input

Control input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: under 2 mA, removable terminal block (14 x 2 pins)

Control output

Control output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: under 10 mA, removable terminal block (14 x 2 pins)

Indicator

Power, 5-segment bargraph level meter, selected zone, emergency zone active, evacuation active, alert active, front panel microphone active, general fault, CPU fault, menu driven LCD for date, IP address, password etc.

Operating humidity

5% to 95% RH (no condensation)

Operating temperature

-5 °C to +45 °C

Finish

Aluminium, Steel plate, hairline, surface-treated, black

Weight

16.5 kg

Accessory (included)

Power cable (2 m) x 1, setting software CD x 1, link cable (3 m) x 2, plastic foot x 4, plastic foot mounting screw x 4, removable terminal plug (14 pins) x 3, removable terminal plug (16 pins) x 1, emergency microphone x 1

Equipment
Tender text