Products

VM-3240VA

System Management Amplifier

  • Master, 1 unit required per system
  • 240 W power output
  • 8 remote microphones max. (4x general + 4x emergency;
  • EN 54: max. 2 x emergency or 4 x general +1 x emergency)
  • 6 zones, for BGM selectable with volume control from the front panel
  • Built-in high quality electronic voice message store for 6 general and 2 emergency messages




  • Specifications
  • Tender text
  • Downloads
Specifications
Specifications for product:
VM-3240VA
Power / current consumption

600 W (at rated output), 260 W (EN 62368-1)

Frequency response

50 Hz - 20 kHz

Rated output

240 W total into 6 zones

Control input

Control input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: under 2 mA, removable terminal block (14 x 2 pins)

Control output

Control output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: under 10 mA, removable terminal block (14 x 2 pins)

Operating temperature

-5 °C to +45 °C

Finish

Aluminium, Steel plate, black

Dimensions

482 x 132.6 x 431.2 mm (W x H x D)

Weight

16.5 kg

Power source

230 V AC, 50 / 60 Hz

Distortion

< 0.7 % (at 1 kHz, rated power)

S/N ratio

85 dB(A) (or more)

Inputs

Input 1 - 3: -50 dBV (MIC) / -10 dB (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female) / phone jack

Input 4: -50 dBV (MIC) / -10 dBV (LINE) (changeable), 600 Ω, electronically balanced, on removable terminal block (14 x 2 pins)

BGM 1 - 2: -10 dBV, 10 kΩ unbalanced, RCA pin jack (2 x 2)

External amplifier Input: 100 V Line, removable terminal block (14 pins)

Outputs

Speaker output 1 – 6: Total within rated output, removable terminal block (14 pins)

Direct output from internal or external amplifier, removable terminal block (16 pins)

Recording output BGM / Paging 0 dBV, 10 kΩ, unbalanced, RCA pin jack

Indicator

Power, 5-segment bargraph level meter, selected zone, emergency zone active, evacuation active, alert active, front panel microphone active, general fault, CPU fault, menu driven LCD for date, IP address, password etc.

Accessory (included)

Power cable (2 m) x 1, setting software CD x 1, link cable (3 m) x 2, plastic foot x 4, plastic foot mounting screw x 4, removable terminal plug (14 pins) x 3, removable terminal plug (16 pins) x 1, emergency microphone x 1

Tender text