Products

VX-3150DS

Emergency Power Supply

  • DC power supply to all system components
  • Combination of built-in power source unit with a high-performance charger
  • Automatical switch to auxiliary battery power if the AC power supply is down
  • VX-3150DS: EN 54-4 certified, Certificate No: 1134-CPR-137




 


  • Specifications
  • Downloads
Specifications
Specifications for product:
VX-3150DS
Power source

220 - 230 V AC, 50 / 60 Hz

Power / current consumption

Approx. 1460 W max. (at rated output with charging),

460 W (EN 60065)

Charging method

Temperature compensated trickle charging

Battery connection

One each positive and negative terminal, applicable cable diameter: AWG 6 – AWG 0 (AWG 1/0) (16 mm2 – 50 mm2)

Line resistance within 4 mΩ / total

Operating temperature

-5 °C to +45 °C

Finish

Steel plate, black

Dimensions

482 x 132.6 x 400.5 mm (W x H x D)

Weight

9 kg

Outputs

DC power output:
8 x 31 V (19 – 33 V) 25 A max. each, M4 screw terminal, distance between barriers: 11 mm


3 x 31 V (19 – 33 V) 5 A max. each, removable terminal block (3 x 2 pins)


1 x 24 V (16 – 25 V) 0.3 A max., removable terminal block (1 x 2 pins

Charging output voltage

27.3 V ±0.3 V (at 25 ˚C), Temperature correction coefficient: -40 mV/ ˚C

Control connector

RJ45 female connector for connecting the system and cascade connection

Shielded Twisted-pair straight cable (TIA/EIA-568A standard)

DS LINK IN/OUT

Type of control signal: Battery check, AC power status, DC power status, charging circuit failure, battery failure, and communication

Panel indicator

AC power IN 1, Charging (Green), Battery power (Green), Battery connect (Green), Battery condition (Green)

Downloads